Kolkata

LOCATION
Kolkata

  • Platform
  • Services
  • Technical
  • About
Current
805 Mb/s
Peak
3.58 Gb/s

Interface & cabling specifications

    Interface & cabling specifications

    Interface type
    CableConnector (*2)WavelengthMax. Distance (*1)Tx (dBm) (*3)Rx (dBm)
    1000Base-SX
    MMLC/PC850 nm250 m-9.5-17
    1000Base-LX (3)
    SMLC/PC1310 nm5km-9.5 ... -3.0-20.0 ... -3.0
    10GEBase-LR
    SMLC/PC1310 nm10 km-8.0 ... 0.5-14.4 ... -0.5
    10GEBase-ER
    SMLC/PC1550 nm40km-4.5 ... 4.0-15.8 ... -1.0
    100GEBase-LR4
    SMLC/PC1310 nm10km-4.5 ... 4.5-8.6 ... 4.5

    Interface & cabling specifications

    Interface typeCableConnector (*2)WavelengthMax. Distance (*1)Tx (dBm) (*3)Rx (dBm)
    10GEBase-LR
    SMLC/PC1310 nm10 km-8.0 ... 0.5-14.4 ... -0.5
    100GEBase-LR4
    SMLC/PC1310 nm10km-4.5 ... 4.5-8.6 ... 4.5
    100GEBase-LR1
    SMLC/PC1310nm10Km+2.5-2.4 … - 4.0
    400GEBase-LR4SMLC/PC1310nm10Km+2.00 … +3.3-10.0 … -13.0
    400GEBase-ZR+SMLC/PC1550nm40Km0.0-10.0 … -20.0

    *(1): This concerns 'customer cable', i.e. the maximum distance between customer equipment and the AMS-IX patch panel. These numbers might be impacted due to connections or equipment capabilities.

    *(2): The connector type depends on the housing site and connector type used in the MMR's

    *(3): As measured at the AMS-IX patch panel

    *(1): This concerns 'customer cable', i.e. the maximum distance between customer equipment and the AMS-IX patch panel. These numbers might be impacted due to connections or equipment capabilities.

    *(2): The connector type depends on the housing site and connector type used in the MMR's

    *(3): As measured at the AMS-IX patch panel